ProSoft ILX34-MBS232 Modbus Serial Communication Module
ProSoft ILX34-MBS232 Modbus Serial Communication Module
0.0
Points
Brand:Allen Bradley PLC Item No.:ILX34-MBS232 Product Origin:USA Product Dimensions:56 x 12 x 75.5 mm Product Weight:0.02 kg Payment:T/T, Western Union, Credit Card Goods_stock:15 Shipping Port:Xiamen, China Lead Time:1-3 Days Condition:Brand New And Original Warranty:1 Year Certificate:COO
The ProSoft ILX34-MBS232 provides a compact communication solution for connecting Modbus serial equipment to Rockwell Automation control systems. Designed for CompactLogix L1 processors and POINT I/O adapter applications, it allows users to incorporate RS-232 devices into a Logix project while keeping communication configuration and diagnostic information accessible through the controller.
In a typical installation, the module is mounted on a compatible POINT I/O wiring base and connected to the serial equipment through its RS-232 interface. The controller project defines the Modbus communication role, serial parameters, node address, and data exchange requirements. Once configured, the module can transfer register and coil information for use in PLC logic, monitoring functions, and supervisory applications.
The ILX34-MBS232 is particularly useful in systems that combine modern PLC control with existing serial instruments or third-party Modbus equipment. Its Master/Slave flexibility, Add-On Instruction support, and controller-accessible diagnostics make it a practical option for industrial communication upgrades and equipment integration.
Technical Specifications
Parameter
Specification
Brand
ProSoft Technology
Model
ILX34-MBS232
Product Type
Modbus Serial Communication Module
Compatible Platform
CompactLogix L1 and POINT I/O Adapter Systems
Serial Interface
RS-232
Communication Protocol
Modbus
Operating Modes
Modbus Master / Modbus Slave
Modbus Formats
RTU / ASCII
Baud Rates
2,400 / 4,800 / 9,600 / 19,200 / 38,400 bps
Data Size
7 or 8 bits
Stop Bits
1 or 2
Parity
None / Even / Odd
Node Address
1–247
Maximum Data Capacity
Up to 1,000 words
Maximum Modbus Commands
30
Maximum Command Size
Up to 36 words, depending on AOI configuration
Configuration Software
RSLogix 5000 / Studio 5000
Power Supply
10–28.8 VDC
POINTBus Current
75 mA at 5 VDC
Communication Port
1 full-duplex RS-232 port
Status Indicators
Module Status, Network Status, TXD, RXD
Operating Temperature
0 to +55°C
Storage Temperature
-40 to +85°C
Relative Humidity
5–95% RH, non-condensing
Mounting Base
1734-TB / 1734-TBS / 1734-TOP / 1734-TOPS
Dimensions
56 x 12 x 75.5 mm
Weight
0.02 kg / 0.04 lb
Recommended Related Models
Model
Product Type
ILX34-MBS485
Modbus RS-485 Serial Communication Module
1734-232ASC
POINT I/O Serial Interface Module
1734-485ASC
POINT I/O RS-485 Serial Interface Module
1734-AENTR
POINT I/O EtherNet/IP Adapter
1734-TB
POINT I/O Terminal Base
Popular Related Models
Model
Product Type
1769-L16ER-BB1B
CompactLogix 5370 L1 Controller
1769-L18ER-BB1B
CompactLogix 5370 L1 Controller
1734-AENT
POINT I/O EtherNet/IP Adapter
1734-AENTR
POINT I/O Dual-Port EtherNet/IP Adapter
1734-IB8
POINT I/O 8-Point Digital Input Module
1734-OB8
POINT I/O 8-Point Digital Output Module
1734-IE2C
POINT I/O 2-Channel Analog Input Module
1734-OE2C
POINT I/O 2-Channel Analog Output Module
Applications
The ILX34-MBS232 is used in automation systems where CompactLogix L1 controllers or POINT I/O networks need to communicate with RS-232 Modbus devices.
SCADA Integration: Connects serial field equipment to PLC-based supervisory and monitoring systems, supporting centralized data collection and control.
Industrial Instrumentation: Exchanges process data with Modbus-compatible meters, analyzers, sensors, and measurement instruments.
Machine Automation: Links controllers with serial devices used for machine status monitoring, parameter exchange, and operational commands.
Legacy Equipment Connectivity: Helps integrate existing Modbus serial devices into newer Logix-based control architectures.
Distributed I/O Systems: Supports serial communication in POINT I/O installations using compatible adapters.
Process Monitoring: Collects register and coil data from field devices for use in PLC logic, alarms, and operating displays.
Advantages and Key Features
Configurable Modbus Master or Slave Operation
The module can operate as either a Modbus Master or Slave, allowing it to initiate communication with remote devices or respond to requests from another Modbus controller. This flexibility supports different system layouts without changing the basic hardware platform.
RS-232 Serial Communication
The ILX34-MBS232 provides a full-duplex RS-232 interface for point-to-point connections. It is intended for relatively short-distance serial communication, with ProSoft specifying applications up to 50 feet (15.2 meters) from the processor.
Modbus RTU and ASCII Support
The module supports Modbus RTU and ASCII communication modes. RTU uses CRC-16 error checking, while ASCII uses LRC error checking, allowing integration with a range of compatible serial devices.
Flexible Data Exchange
The module supports up to 1,000 words of data and up to 30 Modbus commands, with command sizes dependent on the selected Add-On Instruction configuration. This allows users to organize communication around the data requirements of connected equipment.
Logix Controller Integration
Configuration is performed through RSLogix 5000 or Studio 5000. Its Add-On Instruction creates user-defined data structures for I/O, status, and control information, helping simplify communication management within the controller project.
Integrated Diagnostics
Module and communication status information is available through controller tags. TXD and RXD indicators provide a visual reference for serial activity, while diagnostic data helps identify communication errors and device-response problems.
Configuration Backup
Module configuration can be stored within the CompactLogix project file, helping maintain communication settings as part of the controller application and simplifying project backup and restoration.
Technical FAQs
Q1: What is the primary function of the ILX34-MBS232?
A: It provides an RS-232 serial interface for Modbus communication between CompactLogix L1 or compatible POINT I/O systems and external Modbus devices. It supports both Master and Slave operation.
Q2: Can the module operate as both a Modbus Master and a Modbus Slave?
A: Yes. Its serial port can be configured for either role. In Master mode, it initiates requests to connected devices. In Slave mode, it responds to requests from an external Modbus Master.
Q3: Which Modbus communication modes are supported?
A: The module supports Modbus RTU and ASCII. RTU uses CRC-16 error checking, while ASCII communication uses LRC error checking. RTU operation requires an 8-bit data size.
Q4: Which baud rates are available?
A: The published product specifications list baud rates of 2,400, 4,800, 9,600, 19,200, and 38,400 bps. The communication settings must match those configured on the connected Modbus device.
Q5: How many Modbus commands can the module handle?
A: It supports up to 30 Modbus commands. The maximum data size per command depends on the selected Add-On Instruction configuration, with supported command sizes of up to 36 words.
Q6: Which Modbus function codes are supported?
A: Supported functions include reading coils, discrete inputs, holding registers, and input registers, as well as writing single or multiple coils and registers. Function code 8 is also supported for the specified Slave diagnostic subfunction.
Q7: How is the ILX34-MBS232 configured in a Logix system?
A: Configuration is handled through RSLogix 5000 or Studio 5000 using the module's associated Add-On Instruction and controller data structures. The configuration should be matched to the connected device's Modbus address and serial communication parameters.
Q8: What should be checked if Modbus communication fails?
A: Check the RS-232 wiring, baud rate, parity, data size, stop bits, Modbus mode, and node address. Also review controller diagnostic tags and the TXD/RXD indicators to determine whether requests are being transmitted and responses are being received.
Q9: Does the module require a separate wiring base?
A: Yes. The module is installed with a compatible POINT I/O wiring base, such as the 1734-TB, 1734-TBS, 1734-TOP, or 1734-TOPS. The wiring base is not included with the communication module.
Q10: Can the ILX34-MBS232 be used for long-distance RS-232 communication?
A: It is intended for point-to-point applications with a maximum specified distance of approximately 50 feet (15.2 meters). For applications requiring a different serial interface or longer network reach, an RS-485 solution may be more appropriate.