The GE IC697CMM742-LL Ethernet Interface Module is a Type 2 communication module developed for the Series 90-70 programmable logic controller platform. It provides Ethernet connectivity for PLC applications requiring communication with industrial computers, supervisory systems, and other network-connected automation equipment.

One of its distinguishing characteristics is the availability of three Ethernet connection types: 10Base-T, 10Base2, and AUI. This arrangement gives engineers flexibility when maintaining older industrial network infrastructures. However, the interfaces are alternatives rather than simultaneous connections, so the appropriate port and physical media must be selected for each installation.

The module also includes dedicated serial interfaces for Station Manager access and software loading. Four status LEDs help maintenance personnel assess module health and communication activity, while the restart pushbutton provides a local control for restarting the interface.

For existing Series 90-70 installations, the IC697CMM742-LL remains a relevant spare-parts option when maintaining legacy Ethernet communication infrastructure. Before replacement, engineers should carefully verify CPU firmware compatibility, module revision, rack power capacity, and network connection requirements.

Technical Specifications

Parameter

Specification

Brand

GE Fanuc

Model

IC697CMM742-LL

Product Type

Ethernet Interface Module

Product Family

Series 90-70

Module Classification

Ethernet Interface Type 2

Installation

One slot in Series 90-70 PLC rack

Ethernet Ports

10Base-T, 10Base2, AUI

Network Speed

10 Mbps

Ethernet Standards

IEEE 802.2, IEEE 802.3

Communication

TCP/IP

Station Manager Port

RS-232, 6-pin RJ-11

Software Load Port

RS-485, 15-pin D-sub

Status Indicators

MODULE OK, LAN ONLINE, SERIAL ACTIVE, STATUS

Operating Voltage

+5 VDC and +12 VDC

Typical +5 VDC Current

2.0 A

Maximum +12 VDC Current

0.5 A

Operating Temperature

0°C to +55°C

Internal Fuse

5 × 20 mm, 250 V, 1.0 A slow-acting

Dimensions

233 × 41 × 175 mm

Weight

0.522 kg (1.15 lb)

Recommended Related Models

Model

Product Description

GE IC697CMM742

Series 90-70 Ethernet Interface Type 2 Module

GE IC697CMM741

Series 90-70 Ethernet Interface Module

GE IC697CMM711

Communications Coprocessor Module

GE IC697CPU771

Series 90-70 PLC CPU Module

GE IC697CPU772

Series 90-70 PLC CPU Module

GE IC697PWR711

Series 90-70 PLC Power Supply

These models belong to the Series 90-70 control and communication ecosystem. Their functions and compatibility vary, so verify CPU firmware, rack configuration, and power requirements before selecting replacement hardware.

Popular Related Models

Model

Product Description

GE IC693CMM321

Series 90-30 Ethernet Interface Module

GE IC693CPU364

Series 90-30 CPU with Ethernet Interface

GE IC693CPU374

Series 90-30 CPU with Embedded Ethernet

GE IC697RCM711

Series 90-70 Redundancy Communications Module

GE IC697CMM721

Series 90-70 Communications Module

GE IC697ALG230

Series 90-70 Analog Input Module

GE IC697MDL740

Series 90-70 Discrete Input Module

These products cover communication, processing, and I/O functions across GE Fanuc PLC platforms. They are related automation components, not necessarily direct substitutes for the IC697CMM742-LL.


Applications

The GE IC697CMM742-LL Ethernet Interface Module is designed for the GE Fanuc Series 90-70 PLC platform. It provides Ethernet connectivity between the PLC and industrial computer networks, enabling data exchange, remote monitoring, and communication with other automation equipment.

Typical application areas include:

  • PLC network integration: Connects Series 90-70 controllers to compatible Ethernet networks.

  • Industrial data communication: Supports data exchange between PLC systems and supervisory computers.

  • SCADA connectivity: Provides an Ethernet communication interface for monitoring and control applications.

  • Factory automation: Connects PLC equipment with other network-enabled industrial devices.

  • Remote diagnostics: Supports access to PLC communication information through the Station Manager interface.

  • Legacy system maintenance: Provides a replacement option for existing Series 90-70 installations using the Type 2 Ethernet interface.


Advantages

Multiple Ethernet Connection Options

The module provides 10Base-T, 10Base2, and AUI network interfaces, allowing connection to different Ethernet media used in legacy industrial networks.

Series 90-70 PLC Integration

Designed for installation in a Series 90-70 PLC rack, it provides an established communication interface for compatible controller configurations.

TCP/IP Communication Support

The Ethernet interface supports TCP/IP-based communication, enabling data exchange between PLC equipment and compatible network applications.

Dedicated Diagnostic Interface

Its RS-232 Station Manager port provides access to diagnostic and configuration functions, helping engineers investigate network communication conditions.

Separate Software Loading Port

An RS-485 software loading interface supports the module's software maintenance requirements.

Status Monitoring

Four LED indicators provide information about module operation, network status, serial activity, and reported exceptions.


Technical FAQs

Q1: What is the primary function of the GE IC697CMM742-LL?

It provides a Type 2 Ethernet communication interface for GE Fanuc Series 90-70 PLC systems, enabling the controller to communicate with compatible Ethernet networks.

Q2: Which PLC platform is compatible with this module?

It is designed for the Series 90-70 PLC family. CPU firmware compatibility must be checked before installation. GE recommends CPU firmware version 6.00 or later for full functionality. Restricted operation is documented for certain earlier versions, while firmware earlier than 4.12 is not supported.

Q3: What Ethernet ports are available?

The module provides three network connection options: 10Base-T through an RJ-45 connector, 10Base2 through a BNC connector, and AUI through a 15-pin D-sub connector. Only one network port can be used at a time.

Q4: What is the supported Ethernet communication speed?

The network interfaces operate at 10 Mbps and comply with the relevant IEEE 802.3 Ethernet specifications.

Q5: What is the purpose of the Station Manager port?

The RS-232 Station Manager port provides a local interface for configuration, diagnostics, and monitoring of Ethernet interface functions.

Q6: What is the function of the Software Load port?

The RS-485 Software Load port is used for the module's software loading and maintenance operations.

Q7: What do the four LED indicators represent?

The indicators are MODULE OK, LAN ONLINE, SERIAL ACTIVE, and STATUS. They provide information about module health, network activity, serial communication, and exception conditions.

Q8: How many Ethernet Interface modules can be installed in one Series 90-70 CPU rack?

Up to four Ethernet Interface Type 2 modules can be installed in a Series 90-70 PLC CPU rack, subject to the applicable rack and system configuration requirements.

Q9: What power does the module require?

It receives +5 VDC and +12 VDC from the PLC power supply. Typical current consumption is 2.0 A on the +5 VDC supply, with up to 0.5 A on the +12 VDC supply when powering an external AUI transceiver.

Q10: What should be checked when troubleshooting Ethernet communication failures?

Check the selected network port, cable and transceiver connections, module LEDs, PLC CPU firmware, and Station Manager configuration. Also verify that the network media and connected equipment are compatible with the module's 10 Mbps interface.