Honeywell RM7895A1014 On‑Off Primary Burner Control Module with Prepurge for Industrial Combustion

0.0
Points

Brand:Honeywell DCS
Item No.:Honeywell RM7895A1014
Product Origin:USA
Product Dimensions:127 × 127 × 155 mm
Product Weight:0.90 kg
Payment:T/T, Western Union, Credit Card
Goods_stock:15
Shipping Port:Xiamen, China
Lead Time:1-3 Days
Condition:Brand New And Original
Warranty:1 Year
Certificate:COO

Add to cart

RM7890B1014RM7890B1014RM7890B1014RM7890B1014

The Honeywell RM7895A1014 is a robust on‑off primary burner control module engineered for precision flame supervision, sequenced burner operation, and safety in gas, oil, or combination fuel systems. As part of Honeywell’s respected 7800 Series combustion platform, this controller combines advanced diagnostics, nonvolatile memory, and selectable interlocks to deliver reliable performance for industrial and commercial single‑burner applications. Its modular architecture and compatibility with standard Honeywell subbases, flame amplifiers, and purge timer cards make it a flexible solution for engineered combustion systems where safety and uptime matter most.


Technical Specifications

ParameterSpecification
ModelRM7895A1014
ManufacturerHoneywell
Module TypeOn‑Off Primary Burner Control
Control FunctionsFlame supervision, automatic sequencing, system diagnostics
Power Supply120 VAC, 50/60 Hz
Pilot TypeIntermittent
Flame Establishing PeriodPilot: Selectable 4 or 10 sec; Main: Intermittent
MemoryNonvolatile sequence & diagnostics memory
Diagnostic IndicationMultiple LEDs for status & fault indication
Required ComponentsQ7800A/B subbases, ST7800A purge timer, compatible flame amplifiers
Operating Temperature-40°C to 60°C
Storage Temperature-40°C to 85°C
Dimensions (with Q7800A Subbase)127 × 127 × 133 mm
Dimensions (with Q7800B Subbase)127 × 127 × 155 mm
Weight~0.90 kg
ApprovalsUL Recognized, CSA Certified, FCC Part 15 Class B
HumidityUp to 85% RH non‑condensing
Notes: Dimensions may vary slightly depending on subbase used.

Recommended Related Models

  • Honeywell RM7895A1048

  • Honeywell RM7890A1015

  • Honeywell RM7890A1031

  • Honeywell RM7890B1014

  • Honeywell RM7840L1018

  • Honeywell RM7850A1019


Popular Honeywell Burner Control Modules

  • Honeywell RM7895A1014

  • Honeywell RM7895A1048

  • Honeywell RM7890A1015

  • Honeywell RM7890A1031

  • Honeywell RM7890B1014

  • Honeywell RM7840G1014

  • Honeywell RM7840L1026

  • Honeywell RM7850A1001


Applications

The RM7895A1014 is an ideal burner control for industrial and commercial combustion systems requiring reliable flame supervision and safety sequencing:

  • Industrial steam and hot‑water boilers

  • Commercial furnace and oven systems

  • HVAC burner management systems

  • Combustion chambers in manufacturing processes

  • Thermal processing and heat treatment equipment

  • Gas and oil fired single‑burner installations

Its advanced flame control and diagnostic capabilities support safer and more efficient combustion system management.


Advantages

Comprehensive Flame Safety Logic
Engineered with advanced flame supervision and lockout logic to mitigate unsafe combustion events.

Nonvolatile Diagnostic Memory
Retains operational history and lockout status even after power interruptions, helping service teams with effective troubleshooting.

Flexible Integration
Works seamlessly with Honeywell 7800 Series subbases, flame amplifiers, purge card modules, and optional display interfaces.

Selectable Control Features
Pilot flame establishing period and safety interlocks can be programmed to suit specific burner logic requirements.

Industrial‑Grade Reliability
Designed for heavy industrial use with wide temperature tolerance, robust circuitry, and multiple safety approvals.


Technical FAQs

  1. What type of control is the RM7895A1014?
    It’s an on‑off primary burner control module with built‑in flame supervision and safety sequencing for industrial burners.

  2. What voltage does it operate on?
    The unit runs on a 120 VAC, 50/60 Hz power supply.

  3. Can it be used with both gas and oil burners?
    Yes, it’s designed for automatic gas, oil, or combination fuel single‑burner systems.

  4. Does it support diagnostic memory?
    Yes, nonvolatile memory retains flame status and sequence history after power loss.

  5. What safety interlocks are available?
    Selectable interlocks allow customization of flame failure responses and lockout behavior.

  6. Is this module compatible with Honeywell flame amplifiers?
    Yes, it works with various 7800 Series flame signal amplifiers.

  7. Can optional display modules be added?
    Yes, it supports keyboard display modules, remote annunciators, and data interfaces.

  8. What is the operating temperature range?
    Rated for operation from -40°C to +60°C.

  9. How is installation handled?
    Mounts in a compatible Q7800A or Q7800B subbase with plug‑in design for efficient field servicing.

  10. What happens if flame fails during operation?
    It initiates a safety lockout to prevent unsafe burner conditions.