The Honeywell AMPS-24E Addressable Power Supply is part of the NOTIFIER fire alarm product range. It combines power distribution, battery charging, and addressable supervision in one unit, making it suitable for compatible fire detection and life-safety installations.

The unit is designed for systems that require additional power capacity while maintaining communication with the fire alarm control panel. Its FlashScan and CLIP compatibility allows it to operate within supported NOTIFIER system architectures. Battery charging and monitoring functions also help maintain secondary power readiness during normal system operation.

The AMPS-24E is the 220–240 VAC version of the AMPS-24 family. When selecting a replacement, confirm the input voltage, connected fire alarm panel, communication protocol, battery configuration, and output requirements. Fire alarm equipment should be installed and commissioned by qualified personnel in accordance with applicable codes and manufacturer instructions.

Technical Specifications

Parameter

Specification

Brand

Honeywell / NOTIFIER

Model

AMPS-24E

Product Type

Addressable Power Supply

Product Category

Fire Alarm System Power Supply

AC Input Voltage

220–240 VAC

Frequency

50/60 Hz

Communication Protocols

FlashScan / CLIP

Battery Charging

Selectable charging current

Supported Battery Capacity

7–200 Ah

Dimensions

175 × 55 × 150 mm

Weight

1.93 kg / 4.25 lb

Note: Output-current limits depend on the selected battery size, charging-current setting, and power-output configuration. Consult the applicable installation manual before designing or modifying the system.

Recommended Related Models

The following NOTIFIER products are relevant to AMPS-24E system applications. They perform different functions and should be selected according to the fire alarm system architecture.

Model

Product Type

Application

AMPS-24

Addressable Power Supply

120 VAC version of the AMPS power supply family

NFS2-3030

Intelligent Fire Alarm Control Panel

Central fire detection and system control

NFS-3030

Intelligent Fire Alarm Control Panel

Addressable fire alarm system management

NCA-2

Network Control Annunciator

Network-level system display and control

Popular Related Models

These NOTIFIER components may also be considered when maintaining or expanding a compatible fire alarm installation.

Model

Product Type

Application

NCD-2

Network Control Display

Fire alarm network status display and control

CPU2-3030

Fire Alarm Control Panel CPU

Main processing unit for compatible control panels

CPS-24

Power Supply Board

Power supply and battery charging functions within the AMPS-24/E assembly

Before ordering a replacement, verify the exact model, AC input voltage, board configuration, connected panel, and applicable fire alarm system approvals.


Applications

The Honeywell NOTIFIER AMPS-24E is an intelligent addressable power supply and battery charger designed for fire alarm and life-safety systems. It provides auxiliary power for compatible fire alarm equipment and supports system operation through an addressable communication interface.

The AMPS-24E can operate with compatible NOTIFIER fire alarm control panels using FlashScan or CLIP communication protocols. It can also serve as a power supply for the NCA-2 Network Control Annunciator.

Typical applications include:

  • Fire alarm control systems: Providing additional power for compatible fire alarm system components.

  • Large commercial buildings: Supporting power distribution in integrated fire detection installations.

  • Industrial facilities: Supplying compatible equipment in fire alarm and life-safety systems.

  • Network annunciator installations: Supporting the NCA-2 Network Control Annunciator.

  • Remote power arrangements: Providing supervised power and battery charging for compatible remote equipment.


Key Features and System Benefits

The AMPS-24E combines addressable power management with battery charging and system supervision functions.

  • Addressable communication: Supports FlashScan and CLIP protocols for communication with compatible fire alarm control panels.

  • 220–240 VAC input: Designed for AC power installations using the AMPS-24E voltage configuration.

  • Battery charging capability: Supports compatible sealed lead-acid battery arrangements, with selectable charging current.

  • Power output flexibility: Provides multiple DC output arrangements for compatible system equipment.

  • Power supervision: Monitors relevant power conditions, including AC power loss and battery-related faults.

  • Brownout detection: Helps identify low-voltage conditions affecting the power supply.

  • Isolated SLC interface: Provides an isolated Signaling Line Circuit interface for addressable system communication.

  • System integration: Designed for use with compatible NOTIFIER fire alarm control panels and network annunciators.


Technical FAQs

Q1: What is the primary function of the Honeywell AMPS-24E?

The AMPS-24E is an addressable power supply and battery charger. It provides DC power for compatible fire alarm equipment while communicating system status through an addressable interface.

Q2: What is the difference between AMPS-24 and AMPS-24E?

The main difference is the AC input voltage configuration. The AMPS-24 is designed for 120 VAC applications, while the AMPS-24E is designed for 220–240 VAC, 50/60 Hz installations.

Q3: Which communication protocols does the AMPS-24E support?

It supports NOTIFIER FlashScan and CLIP (Classic Loop Interface Protocol) operating modes. The selected mode must be compatible with the connected fire alarm control panel.

Q4: Which fire alarm control panels can work with the AMPS-24E?

The AMPS-24/E is designed for compatible NOTIFIER systems, including the NFS-3030 and NFS2-3030 fire alarm control panels. It can also be used as a power supply for the NCA-2 Network Control Annunciator in supported configurations.

Q5: Does the AMPS-24E include a battery charger?

Yes. It includes a charging circuit for compatible sealed lead-acid batteries. Charging current is selectable according to the system configuration and battery requirements.

Q6: What battery capacity can the AMPS-24E support?

The manufacturer's documentation specifies support for battery capacities from 7 Ah to 200 Ah, subject to the selected charging configuration and applicable installation requirements.

Q7: What happens if the AC power supply fails?

The system can report AC power loss through its supervision functions. The connected battery arrangement provides secondary power when configured correctly and within the system's specified operating limits.

Q8: What is the purpose of the isolated SLC interface?

The isolated Signaling Line Circuit interface supports addressable communication between the power supply and compatible fire alarm control equipment.

Q9: What should be checked if the AMPS-24E reports a power fault?

Inspect the AC input, battery connections, battery condition, output wiring, fuse status, and system configuration. Review the fire alarm control panel's trouble information to help identify the reported fault.

Q10: Can the AMPS-24E replace a standard 24 VDC power supply?

Not automatically. It is an addressable fire alarm power supply with specific communication, charging, and supervision functions. Any replacement must meet the original system's electrical, functional, and certification requirements.