Allen Bradley 20BD248A0ANNAND0 PowerFlex 700 AC Drive
Allen Bradley 20BD248A0ANNAND0 PowerFlex 700 AC Drive
0.0
Points
Brand:Allen Bradley PLC Item No.:20BD248A0ANNAND0 Product Origin:USA Product Dimensions:976.3 x 403.9 x 275.5 mm Product Weight:71.44 kg Payment:T/T, Western Union, Credit Card Goods_stock:15 Shipping Port:Xiamen, China Lead Time:1-3 Days Condition:Brand New And Original Warranty:1 Year Certificate:COO
The Allen Bradley 20BD248A0ANNAND0 is a high-capacity PowerFlex 700 AC Drive intended for large industrial motor applications. Its 480 VAC three-phase input and 248 A continuous output make it suitable for substantial motor loads.
The drive's configuration combines vector control with 120V I/O and does not include a communication module or motor-feedback option. It also has no brake IGBT or internal brake resistor. These characteristics are important when determining whether the drive is suitable for a particular retrofit or replacement project.
The integrated EMC filter and common-mode choke are intended to support the specified electromagnetic compatibility requirements. Installation should nevertheless follow appropriate cabinet, grounding, cable-routing, and motor-cable practices.
For maintenance engineers, the complete catalog number is especially important. The 20BD248A0ANNAND0 should not automatically be treated as interchangeable with another 248 A PowerFlex 700 configuration because changes in suffixes can indicate different control, communication, feedback, or other options.
Rockwell Automation has discontinued the PowerFlex 700 20B product family, with the 20BD248A0ANNAND0 listed as discontinued. For existing installations, this makes accurate identification particularly important when sourcing replacement equipment, spare drives, or engineering replacements.
Technical Specifications
Specification
Details
Brand
Allen Bradley
Manufacturer
Rockwell Automation
Model
20BD248A0ANNAND0
Product Family
PowerFlex 700
Product Type
AC Drive / Variable Frequency Drive
Drive Series
PowerFlex 700
Input Voltage
480 VAC
Input Phase
3 Phase
Output Current
248 A Continuous
Output Current, 1 min
273 A
Output Current, 3 sec
372 A
Normal-Duty Rating
200 HP
Heavy-Duty Rating
150 HP
Frame Size
Frame 6
Enclosure
IP20 / Type 1, Conformal Coating
Control
Vector Control with 120V I/O
Feedback
No Feedback
Brake IGBT
No
Internal Brake Resistor
No
Communication Module
No
EMC Filtering
EMC Filter with Common-Mode Choke
Dimensions
976.3 × 403.9 × 275.5 mm
Weight
71.44 kg (157.50 lb)
Dimensions: 976.3 × 403.9 × 275.5 mm Weight: 71.44 kg (157.50 lb)
The exact installation should be evaluated according to the motor's electrical characteristics, load profile, duty classification, cabinet environment, control voltage, braking requirements, and communication requirements.
Recommended Related Models
The following PowerFlex 700 models are useful for comparison in industrial drive replacement and maintenance projects:
Allen Bradley 20BD248A0ANNANA0 PowerFlex 700 AC Drive
Allen Bradley 20BD180A0ANNANC0 PowerFlex 700 AC Drive
Allen Bradley 20BD180A0ANNAND0 PowerFlex 700 AC Drive
Allen Bradley 20BD180A0ANNAND1 PowerFlex 700 AC Drive
Allen Bradley 20BD180A0AYNANC0 PowerFlex 700 AC Drive
Allen Bradley 20BD180A0AYNAND0 PowerFlex 700 AC Drive
Allen Bradley 20BD180A3ANNANC0 PowerFlex 700 AC Drive
Allen Bradley 20BD180A3ANNANC1 PowerFlex 700 AC Drive
Allen Bradley 20BD180A3ANNAND0 PowerFlex 700 AC Drive
Popular Related Models
Allen Bradley 20BD156A3ANNAND0 PowerFlex 700 AC Drive
Allen Bradley 20BD156A3ANNANC1 PowerFlex 700 AC Drive
Allen Bradley 20BD156A3ANNAND1 PowerFlex 700 AC Drive
Allen Bradley 20BD180A0ANNANC0 PowerFlex 700 AC Drive
Allen Bradley 20BD180A0ANNAND0 PowerFlex 700 AC Drive
Allen Bradley 20BD180A0ANNAND1 PowerFlex 700 AC Drive
Allen Bradley 20BD180A0AYNANC0 PowerFlex 700 AC Drive
Allen Bradley 20BD180A0AYNAND0 PowerFlex 700 AC Drive
Allen Bradley 20BD248A0ANNANA0 PowerFlex 700 AC Drive
Allen Bradley 20BD248A0ANNANC0 PowerFlex 700 AC Drive
Applications and Industrial Motor Control
The Allen Bradley 20BD248A0ANNAND0 is a PowerFlex 700 AC Drive designed for large industrial motor-control applications. This configuration operates from a 480 VAC, three-phase supply and provides 248 A continuous output current, with a 200 HP normal-duty rating and 150 HP heavy-duty rating.
The drive uses a Frame 6 architecture, IP20 / Type 1 enclosure with conformal coating, and vector control with 120V I/O. It is configured without a communication module, brake IGBT, internal brake resistor, or motor feedback. An EMC filter with common-mode choke is included for the specified second-environment installation requirements.
Typical applications include:
Large conveyor and material-handling systems
Industrial pumps and fluid-processing equipment
Fans and ventilation systems
Compressors and large rotating machinery
Manufacturing and production lines
Packaging and processing equipment
Process-control machinery
Heavy industrial motor applications
PowerFlex 700 retrofit projects
Industrial drive replacement and maintenance
This configuration is particularly relevant where a high-current PowerFlex 700 drive is required and the existing control architecture is based on 120V I/O.
Key Features and Industrial Advantages
248 A continuous output
The drive provides 248 A continuous output current, with 273 A available for one minute and 372 A for three seconds under the specified normal-duty conditions.
480 VAC three-phase operation
The 20BD248A0ANNAND0 is designed for 480 VAC, three-phase industrial power systems and is suitable for large motor applications within its rated operating range.
200 HP normal-duty rating
The configuration provides a 200 HP normal-duty rating and 150 HP heavy-duty rating, allowing engineers to select the appropriate duty classification according to the application.
Vector control with 120V I/O
The drive uses vector control with 120V I/O, providing a practical interface for industrial control panels and existing automation systems using this control-voltage architecture.
Frame 6 design
The Frame 6 construction accommodates the drive's high-current industrial application and is appropriate for larger motor-control installations.
EMC filtering and common-mode choke
The drive includes an EMC filter with common-mode choke, supporting electromagnetic compatibility requirements for the specified second-environment installation.
No internal braking hardware
This configuration does not include a brake IGBT or internal drive-mounted brake resistor. Applications requiring braking or regenerative-energy management need to be engineered accordingly.
No internal communication module
The base configuration does not include a communication module. Where networked control is required, the system architecture should be reviewed to determine the appropriate communication solution.
10 Technical FAQs
1. What is the output rating of the 20BD248A0ANNAND0?
The drive provides 248 A continuous output current. Its normal-duty rating is 200 HP, while the heavy-duty rating is 150 HP.
2. What is the input voltage of this PowerFlex 700 drive?
The 20BD248A0ANNAND0 is designed for a 480 VAC, three-phase input supply. The incoming plant power should be verified before installation.
3. What type of control does this model use?
This configuration uses vector control with 120V I/O. The PowerFlex 700 platform also supports configurable motor-control functions appropriate to different industrial applications.
4. Does the drive have an internal brake resistor?
No. The 20BD248A0ANNAND0 is specified without an internal drive-mounted brake resistor and without a brake IGBT. External braking equipment may be required for applications with specific stopping or regenerative requirements.
5. Does this model include a communication module?
No internal communication module is included in this configuration. The drive should therefore be evaluated together with the intended control architecture when network communication is required.
6. Does the drive use motor feedback?
The specified configuration is without feedback. Its vector-control operation is therefore configured for applications that do not require an external motor-feedback device.
7. What should be checked if the drive experiences an overcurrent fault?
Inspect the mechanical load, motor condition, output wiring, acceleration settings, and motor parameters. Excessive load or incorrect configuration can cause the drive to reach its current protection limits.
8. What motor data should be entered during commissioning?
The actual motor nameplate should be used for applicable voltage, current, frequency, speed, and other required motor parameters. Accurate data is particularly important when configuring vector-control operation.
9. How should this drive be integrated with an existing PLC?
Because this configuration uses 120V I/O and does not include an internal communication module, the control system should be designed around the available hardwired I/O or an appropriate separately installed communication solution.
10. What should be verified before replacing an existing PowerFlex 700?
Check the complete catalog number, input voltage, output current, motor horsepower, duty rating, I/O voltage, control method, feedback requirements, communication architecture, braking requirements, enclosure, and installed options. Existing parameters should also be documented before removing the original drive.