Brand:Siemens Item No.:6AG1315-6FF04-2AB0 Product Origin:Germany Product Dimensions:40 × 125 × 130 mm Product Weight:0.344 kg Payment:T/T, Western Union, Credit Card Goods_stock:15 Shipping Port:Xiamen, China Lead Time:1-3 Days Condition:Brand New And Original Warranty:1 Year Certificate:COO
The Siemens 6AG1315-6FF04-2AB0 SIPLUS S7-300 CPU 315F-2DP is a fail-safe programmable logic controller designed for industrial automation systems requiring dependable processing, distributed communication, and additional environmental protection. Based on the 6ES7315-6FF04-0AB0 platform, it provides 384 KB of work memory, an integrated MPI interface, and a second PROFIBUS DP master/slave interface.
One of the key characteristics of this CPU is its integrated fail-safe functionality. It supports safety-related automation tasks alongside standard PLC operations when used with the appropriate Siemens engineering software and a properly validated safety configuration.
The SIPLUS design incorporates conformal coating and supports an operating temperature range of -25 to +60°C. Its integrated 24 V DC power supply also simplifies installation within compatible S7-300 control systems.
For industrial system integrators and maintenance engineers, the 6AG1315-6FF04-2AB0 is a practical option for applications requiring a compact fail-safe controller with PROFIBUS DP connectivity. It is particularly relevant to existing S7-300 installations where PROFINET communication is not required.
Technical Specifications
Parameter
Specification
Manufacturer
Siemens
Model
6AG1315-6FF04-2AB0
Product Family
SIPLUS S7-300
CPU Type
CPU 315F-2DP
Product Type
Fail-Safe PLC CPU Module
Base Model
6ES7315-6FF04-0AB0
Work Memory
384 KB
First Interface
MPI
Second Interface
PROFIBUS DP
PROFIBUS Function
DP Master / Slave
PROFIBUS DP Speed
Up to 12 Mbps
Integrated Power Supply
24 V DC
Permissible Supply Range
19.2–28.8 V DC
Memory Card
Micro Memory Card required
Programming Software
STEP 7 V5.5 SP1 or higher
Safety Engineering
Distributed Safety
Environmental Protection
Conformal coating
Operating Temperature
-25 to +60°C
Dimensions (W × H × D)
40 × 125 × 130 mm
Weight
0.344 kg / 0.76 lb
Recommended Related Models
The following Siemens CPUs are relevant when comparing fail-safe functionality, communication interfaces, and environmental specifications within the SIPLUS S7-300 family.
Model
Product Description
6AG1315-6FF04-2AY0
SIPLUS S7-300 CPU 315F-2DP (EN 50155)
6AG1315-2FJ14-2AB0
SIPLUS S7-300 CPU 315F-2PN/DP
6AG1315-2FJ14-2AY0
SIPLUS S7-300 CPU 315F-2PN/DP (EN 50155)
6AG1317-6FF04-2AB0
SIPLUS S7-300 CPU 317F-2DP
6ES7315-6FF04-0AB0
SIMATIC S7-300 CPU 315F-2DP
Popular Related Models
For S7-300 system maintenance, safety-control upgrades, and spare-part planning, these Siemens models may also be worth considering:
Siemens 6AG1315-2AH14-2AY0 – SIPLUS S7-300 CPU 315-2DP
Siemens 6AG1315-2EH14-2AY0 – SIPLUS S7-300 CPU 315-2PN/DP
Siemens 6AG1315-2FJ14-2AB0 – SIPLUS S7-300 CPU 315F-2PN/DP
Siemens 6AG1317-2FK14-2AB0 – SIPLUS S7-300 CPU 317F-2PN/DP
Siemens 6AG1317-6FF04-2AB0 – SIPLUS S7-300 CPU 317F-2DP
Siemens 6ES7315-2FJ14-0AB0 – SIMATIC S7-300 CPU 315F-2PN/DP
Siemens 6ES7317-6FF04-0AB0 – SIMATIC S7-300 CPU 317F-2DP
Applications
The Siemens 6AG1315-6FF04-2AB0 is a SIPLUS S7-300 CPU 315F-2DP designed for industrial automation systems that require standard PLC processing and integrated fail-safe control functions. Based on the 6ES7315-6FF04-0AB0 platform, this CPU combines 384 KB of work memory with MPI and PROFIBUS DP communication capabilities.
Unlike the CPU 315F-2PN/DP models, this version uses PROFIBUS DP as its second communication interface rather than integrated PROFINET. Its fail-safe functionality makes it suitable for automation architectures where safety-related control and distributed field communication are important.
Typical applications include:
Industrial machine safety: Supports safety-related control functions in appropriately engineered and validated automation systems.
Manufacturing equipment: Coordinates machine sequences, production operations, and equipment interlocks.
Distributed I/O systems: Communicates with compatible remote I/O stations through PROFIBUS DP.
Material handling systems: Supports control applications involving conveyors, transfer equipment, and automated machinery.
Industrial process control: Executes PLC logic and coordinates connected field devices.
Existing S7-300 installations: Provides a SIPLUS fail-safe CPU option for compatible systems operating in demanding environmental conditions.
Advantages
1. Integrated Fail-Safe Control
The CPU 315F-2DP supports standard PLC operations and safety-related automation functions. This allows engineers to implement coordinated control and safety tasks within a compatible SIMATIC S7-300 architecture.
2. PROFIBUS DP Communication
Its integrated MPI interface and second PROFIBUS DP master/slave interface support communication with compatible automation devices and distributed I/O stations.
3. 384 KB Work Memory
The CPU provides 384 KB of work memory for program execution and data processing, making it suitable for a range of medium-complexity S7-300 control applications.
4. Integrated 24 V DC Power Supply
The module includes an integrated 24 V DC power supply, simplifying the power arrangement within compatible S7-300 installations.
5. SIPLUS Environmental Protection
Conformal coating provides additional protection for electronic components against environmental influences. The specified operating temperature range of -25 to +60°C supports installations exposed to wider temperature variations than conventional indoor control environments.
6. Established Siemens Engineering Platform
The CPU can be configured using Siemens STEP 7 engineering software, with Distributed Safety required for fail-safe application engineering. This supports maintenance and integration within compatible S7-300 projects.
Technical FAQs
Q1: What is the main function of the Siemens 6AG1315-6FF04-2AB0?
It is a fail-safe central processing unit for SIMATIC S7-300 automation systems. It executes standard PLC programs and supports safety-related control functions in appropriately configured applications.
Q2: What does CPU 315F-2DP mean?
The 315F designation identifies a CPU 315 with fail-safe functionality. The 2DP designation indicates its integrated MPI interface and additional PROFIBUS DP communication interface.
Q3: How much work memory does this CPU provide?
The module has 384 KB of integrated work memory for PLC program execution and data processing.
Q4: Does the 6AG1315-6FF04-2AB0 support PROFINET?
No. This model uses MPI and PROFIBUS DP interfaces. Applications requiring integrated Ethernet PROFINET communication should consider a compatible CPU 315F-2PN/DP model.
Q5: Can the CPU operate as a PROFIBUS DP master and slave?
Yes. Its second interface supports PROFIBUS DP master and slave communication, allowing integration with compatible distributed automation devices.
Q6: Is a Micro Memory Card required?
Yes. A compatible Siemens Micro Memory Card is required for operation and stores the user program and relevant configuration data.
Q7: Which software is required for programming this CPU?
The specified engineering options include STEP 7 V5.5 SP1 or higher, or STEP 7 V5.2 SP1 or higher with HSP 218, together with Distributed Safety for fail-safe engineering.
Q8: What is the role of the integrated 24 V DC power supply?
It provides the CPU's required DC supply within the S7-300 installation. The external supply must remain within the specified permissible voltage range and installation requirements.
Q9: What should be checked if PROFIBUS DP communication fails?
Check the bus cable, connector wiring, termination resistors, station addresses, transmission rate, and network configuration. Also inspect diagnostic information from the CPU and connected DP devices.
Q10: Can this CPU replace a Siemens CPU 315F-2PN/DP?
Not as a direct like-for-like replacement. The 6AG1315-6FF04-2AB0 uses PROFIBUS DP interfaces and does not provide the integrated PROFINET interface found on CPU 315F-2PN/DP models. Hardware configuration, network architecture, safety program, and application requirements must be reviewed before replacement.